MIL-DTL-87107E
4.5.1.1.2 Results. The fuel sample is acceptable if all the following criteria are met:
a. The maximum visual rating of the heated tube deposits is less than a code 3.
b. The visual rating of the heater tube show neither peacock type deposit (code P) nor abnormal
type deposits (code A).
c. The maximum differential pressure across the test filter does not exceed 10 millimeters of
mercury (mm Hg).
4.5.1.1.3 ASTM D3241 reported data. The following data shall be reported:
a. Differential pressure in mm Hg at 150 minutes, or time to differential pressure of 10 mm Hg,
whichever occurs first.
b. Heater tube deposit visual rating code at the end of the test.
5.
PACKAGING
5.1 Packaging. For acquisition purposes, the packaging requirements shall be as specified in
the contract or order (see 6.2). When packaging of materiel is to be performed by DoD or in-house
contractor personnel, these personnel need to contact the responsible packaging activity to ascertain
packaging requirements. Packaging requirements are maintained by the Inventory Control Point's
packaging activities within the Military Service or Defense Agency, or within the military service's system
commands. Packaging data retrieval is available from the managing Military Department's or Defense
Agency's automated packaging files, CD-ROM products, or by contacting the responsible packaging
activity.
6.
NOTES
(This section contains information of a general or explanatory nature that may be helpful, but is not
mandatory.)
6.1 Intended use. The fuel covered by this specification is intended for use in military gas
turbine engines or military ramjet engines for missile application.
6.2 Acquisition requirements. Acquisition documents must specify the following:
a. Title, number, and date of the specification.
b. Quantity required and size containers required.
c.
Level of packaging and packing required.
d. When blocking and bracing is specified.
6.2.1 Additive. Type and amount of additive (3.3).
6.3 Precaution of mixing additives. To prevent any possible reaction between the concentrated
forms of the different additives (3.3) the fuel contractor is cautioned not to commingle additives prior to
their addition to the fuels.
6.4 Subject term (key word) listing.
exo-Tetrahydrodicyclopentadiene
Missile Fuel
Ramjet
6.5 Material Safety Data Sheets. Contracting officers will identify those activities that require
copies of completed Material Safety Data Sheets (MSDS) prepared in accordance with FED-STD-313.
The pertinent Government mailing addresses for submission of data are listed in FED-STD-313.
6.6 Changes from previous issue. Marginal notations are not used in this revision to identify
changes with respect to the previous issue due to the extent of the changes.
6
For Parts Inquires call Parts Hangar, Inc (727) 493-0744
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business